| CHARACTERISTICS |
|
| INPUT PARAMETERS |
|
| Nominal DC Power [kW] |
6.2 |
| Max. Recommended DC Power [kW] |
6.9 |
| Operating Input Voltage Range [V] |
0.7xVstart - 580 (360 nominal) |
| Full Power MPPT input voltage range (symmetrical load) [V] |
180-530 |
| Full asymmetrical load input voltage range [V] |
220-530 (@ 4kW) / 120-530 (@ 2,2kW) |
| Absolute Max. Input Voltage [V] |
600 |
| Activation voltage "Vstart" [V] |
200 nominal (adjustable within the range 120Vdc-350Vdc,
independently/each input) |
| No of independent MPPT trackers |
2 |
| Max. Input Power, each MPPT [kW] |
4 |
| No. of DC Inputs |
4 (2 each MPPT) |
| Max. DC Current, each MPPT [A] |
18 ( 22 short circuit ) |
| DC Connection |
8 x MultiContact Ř 4mm (4 male - positive input + 4 female - negative input)
Mating cable connector included
Conductor cross section: 4-6mmq/AWG12-10 - Cable Ř w/insulator: 3-6mm |
| INPUT PROTECTION |
|
| Reverse polarity protection |
Yes |
| Fuse rating, each input (-FS suffi x versions only) |
NA |
| DC side varistors |
4 ( 2 for each MPPT ), thermally protected |
| PV array Insulation Control |
according to VDE0126-1-1 |
| DC Switch (-S/-FS suffi x versions only) |
Integrated (Max. Voltage Rating : 600Vdc / Max Current Rating: 25A) |
| OUTPUT PARAMETERS |
|
| Nominal AC Power [up to 40°C, kW] |
6 |
| Max. AC Power [kW] |
6 |
| AC Grid Connection |
single phase ( Live, Neutral, PE ) |
| Nominal AC Voltage [V] |
230 nominal |
| Maximum AC Voltage Range [V] |
180-264 |
| Nominal AC Frequency [Hz] |
50 |
| Max. AC Line Current [A] |
30 |
| AC Connection |
Cage-clamp terminal block
Conductor Cross Section: Solid: 0,5-16mmq / Stranded: 0,5-10mmq / AWG20-6
Cable Gland: M32 - Cable Ř: 13-21mm |
| Line Power Factor |
1 |
| AC Current Distortion [THD%] |
<3.5% at rated power with sine wave voltage |
| OUTPUT PROTECTION |
|
| AC side varistors |
2, plus gas arrester to ground |
| Ground fault protection (AC + DC leakage current) |
according to VDE0126-1-1 |
| CONVERSION EFFICIENCY |
|
| Max. Effi ciency |
97% |
| Euro Effi ciency |
96.4% |
| ENVIRONMENTAL PARAMETERS |
|
| Cooling |
Natural Cooling |
| Ambient Temp. Range [C] |
-25 / + 60 (output power derating above 50C) |
| Operating Altitude [m] |
2000 |
| Acoustical Noise [dBA] |
|
| Environmental IP Rating IP65 |
<50 @1mt |
| Relative Humidity |
0-100% condensing |
| MECHANICAL |
|
| Dimensions [H x W x D] |
740 x 325 x 195 |
| Weight [kg] |
26 |
| OTHER |
|
| Stand-By Consumption [W] |
8 |
| Feed In Power Threshold [W] |
10 |
| Night Time consumption [W] |
0.3 |
| Isolation |
No isolation, Transformer-less |
| Display |
YES (Alphanumeric 2 lines) |
| Communication |
RS485 (cage-clamp connector - Conductor cross section:
0.08-1.5mmq/AWG28-16); RS232 (DB9)
Optional “Aurora Easy Control” remote monitoring system |
| AVAILABLE PRODUCT VARIANTS |
|
| Standard |
no options |
| With DC switch |
PVI-6000-OUTD-S |
| With DC switch and protection fuse/each input |
NA |