Conergy 5400Watt Grid Connect Inverter

Grid Connect Inverter - Max Input = 6.7KW, Max Output = 5.0 KW
The Conergy WR series combines contemporary design withthe technology of the future. The integrated display - a standardfeature on all models in the series - provides access toall relevant system variables. Data logging and communicationwith Conergy WR inverters are possible at any timeusing a plug-and-play slot-in card system. It is no problem toadd desired plug-in cards, e.g. for data transmission, at alater date.

A wide power input range and high efficiency make the Conergy WR series ideal for flexible system dimensioning with all Conergy modules. All Conergy WR inverters are fully compatible in combination with each other for higher system outputs.

Warranty

  • 5 Year Warranty

Technical Specifications

Input Characteristics
MPP voltage range - Vmpp 150 - 400 V
Max DC voltage - VDC max 530 V
Max power - PDC 5430 V
Recommended max PV output - PDC max 6700 Wp
Max input current 35.8 A
Output Characteristics
Mains voltage - VAC 230 V
Frequency - F 50 Hz
Nominal power - PAC 4600 W
Max power PAC 5000 W
Harmonic distortion factor - k < 3.5 %
Max efficiency 94.3 %
General Data
Dimensions 610H x 344W x 220D mm
Weight 16 kg
Cooling Regulated forced ventilation
Temperature -20°C to 50°C
Protective Devices
Ingress protection IP 21 'Optional IP 45'
DC Isolation measurement Warning at RISO < 500 k Ohm
DC Surge voltage protection Integrated
Inverse polarity protection Integrated
Behavior on DC overload Shift the operating point