Ritar 6x2Volt 800Ah GEL Deep Cycle Battery
RL2-800DG is GEL Deep Cycle type, especially designed for frequent deep cycle use and high temperature environment. By using strong grid and specific alloy, this series battery have up to 40%more cycliclife than same AGM model.
Applications
- Communication equipment
- Telecommunication control equipment
- Emergency lighting systems
- Electric power systems
- Power station
- Nuclear power station
- Solar powered and wind powered systems
- Load leveling and storage equipment
- Marine equipment
- Power generation plants
- Alarm systems
- Uninterruptible power supplies and stand-by power for computers
- Medical equipment
- Fire and security systems
- Control equipment
- Stand-by electric power
Features
- Low self-discharge
- Good consistence on deep discharge
- Super long cyclic life
- Free from erosion, pollution, gas escape, and leakage
- Beneficial to environmental protection.
Warranty
- 3 Years Warranty
Technical Specifications
Electrical Characteristics | |
---|---|
Cells Per Unit | 1 |
Voltage Per Unit | 2 |
Capacity | 800Ah at 10hr rate to 1.75 per cell at 25ºC |
Max. Discharge Current | 3000A (5 sec) |
Internal Resistance | 1.20 mΩ |
Operating Temperature Range | Discharge: -30ºC to 60ºC |
Charge: -20ºC to 50ºC | |
Storage: -30ºC to 60ºC | |
Normal Operating Temperature Range | 25ºC ± 5ºC |
Float charging Voltage | 2.25 to 2.30 VDC/unit average at 25ºC |
Recommended maximum charging current limit | 160A |
Equalization and Cycle Service | 2.35 to 2.38 VDC/unit average at 25ºC |
Self Discharge | RITAR batteries can be stored for more than 12 months at 25ºC. Please charge batteries before using. For higher temperature, the time interval will be shorter. |
Mechanical Characteristics | |
Dimensions | 410L x 175W x 352H mm |
Weight | 58.0 kg |
Terminal | Threat insert and Bolt F10 |
Constant Current Discharge Characteristics Unit: A 25ºC
F.V/Time | 15MIN | 30MIN | 1HR | 2HR | 3HR | 4HR | 5HR | 6HR | 8HR | 10HR |
1.60 V | 1162 | 772 | 483 | 287 | 214 | 171 | 144 | 129 | 104 | 87 |
1.65 V | 1105 | 741 | 462 | 277 | 205 | 165 | 138 | 126 | 99 | 84 |
1.70 V | 1031 | 698 | 453 | 272 | 200 | 163 | 136 | 123 | 98 | 82 |
1.75 V | 915 | 621 | 417 | 257 | 190 | 154 | 130 | 116 | 95 | 81 |
1.80 V | 788 | 572 | 393 | 245 | 183 | 153 | 126 | 115 | 93 | 78 |
1.85 V | 666 | 515 | 364 | 232 | 174 | 141 | 120 | 109 | 88 | 74 |
Constant Power Discharge Characteristics Unit: W 25ºC
F.V/Time | 15MIN | 30MIN | 1HR | 2HR | 3HR | 4HR | 5HR | 6HR | 8HR | 10HR |
1.60 V | 2035 | 1372 | 863 | 519 | 389 | 313 | 265 | 244 | 194 | 165 |
1.65 V | 2016 | 1364 | 860 | 512 | 387 | 310 | 262 | 241 | 192 | 163 |
1.70 V | 1855 | 1269 | 833 | 504 | 375 | 305 | 259 | 236 | 189 | 161 |
1.75 V | 1667 | 1143 | 778 | 482 | 362 | 295 | 248 | 225 | 185 | 157 |
1.80 V | 1435 | 1054 | 733 | 461 | 338 | 286 | 241 | 220 | 178 | 152 |
1.85 V | 1214 | 950 | 676 | 434 | 331 | 263 | 230 | 208 | 171 | 138 |
Charging Procedures - 12V Series
Application | Charge Voltage | Max Charge Current | ||
Temperature | Set point | Allowable range | ||
Cycle Use | 25ºC | 14.2 | 14.1 - 14.3 | 0.3C |
Standby | 25ºC | 13.7 | 13.6 - 13.8 | 0.3C |
Charging Procedures - 6V Series
Application | Charge Voltage | Max Charge Current | ||
Temperature | Set point | Allowable range | ||
Cycle Use | 25ºC | 7.10 | 7.05 - 7.15 | 0.3C |
Standby | 25ºC | 6.85 | 6.8 - 6.9 | 0.3C |
Discharge Current VS Discharge Voltage
Final Discharge Voltage V/cell | 1.75 V | 1.70 V | 1.60 V |
Discharge Current A | (A) ≤ 0.2C | 0.2C < (A) < 1.0C | (A) ≥ 1.0C |
Quality and Safety
- Comply with ISO9001:2000 standard
- EMC tested Germany
Details
- Model: 6xRL2 800DG
- Shipping Weight: 348kg
- Manufacturer:
Ritar